AEMC 3731 Clamp-On Ground Resistance Tester
The AEMC 3731 measures ground rod and grid
resistance in any environment without the use of auxiliary ground rods.
Clamp-on ground resistance testers are used on multi-grounded systems
without disconnecting the ground under test. The AEMC 3731 simply clamps
around the ground conductor or rod and measure the resistance to ground
fast and accurately. By performing measurements on installed ground
systems, the user also verifies the quality of the grounding connections
and bonds. Resistance and continuity of grounding loops around pads and
buildings may also be measured.
Features:
-
Simple and fast clamp-on
operation ‚ no leads, no
auxiliary rods or spacing requirements
-
Direct reading of ground
resistance from 0.01Ω to 1200Ω
-
Direct reading of
continuity and ground loop
resistance
-
Direct reading of ground
leakage or phase current from 1mA
to 30Arms
-
Jaw design with large
1.25" (32mm) window ‚
accommodates up to 1000MCM cables
-
Auto-Off for power
management
-
Alarm function with
adjustable set point and buzzer for
quick field checks
-
Memory function to store
99 field measurements for later
retrieval and analysis
-
Meets EN 61010, Cat. III
-
CE Mark and UL approved
-
Rugged Lexan® head and
body construction resists breakage
-
Alarm settings and stored
memory information saved during
shutdown
-
Patented design
Applications:
-
Measure electrical ground
rod and grid resistance
-
Use on multi-grounded
systems without disconnecting the
ground rod under test
-
Measure resistance and
continuity of grounding loops
around pads and buildings
-
Measure leakage current
flowing to ground or circulating in
ground systems
-
Conduct field surveys and
retrieve and analyze readings at a
later time
-
Use on cell towers and telecommunication sites
-
Use on pools, spas and
other consumer installations
| Specifications: |
| Ground
Resistance Ranges |
Auto-Ranging
0.01½ to
1200½ |
|
Range |
0.10 to 1.00Ω |
1.0 to 50.0Ω |
50.0 to
100.0Ω |
100 to 200Ω |
200 to 400Ω |
400 to 600Ω |
600 to 1200Ω |
|
Resolution |
0.01Ω |
0.1Ω |
0.5Ω |
1Ω |
5Ω |
10Ω |
50Ω |
|
Accuracy |
±2% of Reading ± 0.02Ω |
±1.5%
of Reading ± 0.1Ω |
±2%
of Reading ± 0.5Ω |
±3%
of Reading ± 1Ω |
±6%
of Reading ± 10Ω |
±10%
of Reading ± 10Ω |
Approx.
25% of Reading ± 50Ω |
| Current
Measurement Ranges |
Auto-Ranging
1mA to 30.00Arms |
|
Range |
1
to 299mA |
0.300
to 2.999A |
3.00
to 29.99A |
|
|
Resolution |
1mA |
0.001A |
0.01A |
|
Accuracy |
±2.5%
of Reading + 2mA |
±2.5%
of Reading + 2mA |
±2.5%
of Reading + 20mA |
Resistance Measurement Frequency |
2403Hz |
| Resistance
Overload |
OL
displayed above 1200½ |
Current Measurement Frequency |
47
to 800Hz |
| Current
Overload |
OL
displayed above 29.99Arms |
|