Applications
For non-destructive testing of:
- Motors
- Transformers
- Switchgear
- Insulators
- Capacitors
- Power Cables
|
|
DC Dielectric / Hipot Test Set
Features
- Multi-range ammeters to measure leakage current as low as 0.1 µA
- Continuously variable output voltage with multi-range meter
- Fast charging of high-capacitance samples
- Full circuit breaker protection against internal damage due to overload or test sample breakdown
- Guard connection for separating surface leakage losses
- Safety zero start interlock for HV output
- 15-foot shielded HV output cable with guard terminal and 10-foot ground connection cable included
- Meets all specifications that require a full wave rectifier
Specifications
| Output Voltage |
0 to 7.5, 0 to 15 kVDC |
| Maximum Power System Voltage |
7.5 kVac (phase-to-phase) |
| Output Current (Continuous) |
5 mA |
| Display |
Analog meter |
| Weight |
35.2 lbs (16 kg) |
| row 3 column 1 |
row 3 column 2 |
Options
- 220003 - Strip chart recorder
- 222070-62 - High-voltage resistance discharge stick
- 42 - Adjustable overcurrent trip setting on microammeter
- 43 - Adjustable overvoltage trip setting on kilovoltmeter
- 50 - Internal voltage stabilizer
- 56 - Special cable lengths
|