Now Available:
-OP1 Option package 1:
- IEEE-488 / RS232C
- Interface and GUI software
- Remote Inhibit input
- Function Strobe output
|
|
California Instruments 2001RP Programmable AC Power Source
Offering simple rotary front panel
controls, the California Instruments 2001RP programmable AC power source
is ideally suited for a wide range of applications. Selectable input
voltage ranges allow this product to be used anywhere in the world to
provide a convenient source of variable utility power for the testing and
evaluation of domestic and commercial equipment.
All common line voltage and frequency
combinations are covered. In addition, the frequency range extends to 5000
Hz, making these products ideal for commercial and defense avionics
applications. Accurate measurement functions are available as an option to
eliminate the need for external test equipment in many test setups.
Voltage, current, peak current, power, and power factor can be read
directly on the large LCD display or over the bus. Overload protection is
provided standard using a programmable current limit function.
Features:
-
2000 VA Output Power Capable
of handling most single phase applications
-
16 Hz to 5000 Hz Frequency Range Commercial, Military and Avionics applications
-
High Peak Current Capability Drives
a wide variety of non-linear loads
-
Precision Measurements Accurately
measures TRMS Volt, TRMS Current, Peak Current, Crest Factor,
Real Power and Power Factor
-
Remote Control IEEE-488 and
RS232C Interface for automated test applications. Includes Windows
operating software
| Specifications |
| Controller |
|
Type |
Programmable |
|
Controls |
Digital
Encoders |
|
Readouts |
dual
4 digit LCDs |
|
Non
Volatile Setups
(with -OP1 option) |
1
(8) |
| Output |
|
AC Power |
maximum
2000 VA |
|
Load
Connection |
floating
neutral Rear panel terminal block
optional Universal front panel sockets |
|
Voltage |
|
High
range / Low range |
0
- 300 / 0 - 150 V RMS |
|
Accuracy |
16
Hz - 100 Hz ± 0.1 % FS
100 Hz - 5000 Hz ± 0.2 % FS |
|
Resolution |
0.1
V |
|
Load
Regulation |
remote
sense ± 0.1 % FS |
|
Line
Regulation |
10
% Line change ± 0.02 % FS |
|
T.H.D. (into aresistive
load) |
16
Hz - 100 Hz 0.5 typ./ 1.0 max. %
100 Hz - 5000 Hz 1.0 typ./ 2.0 max. % |
|
Output
Noise |
<
0.1 typ. V RMS |
|
Frequency |
|
Range |
16
- 5000 Hz |
|
Accuracy |
±
0.02 % |
|
Resolution |
16.00
Hz - 80.00 Hz 0.01 Hz
80.1 Hz - 800.0 Hz 0.1 Hz
800 Hz - 5000 Hz 1 Hz |
|
Current |
|
RMS
Current |
High
/ Low V range 6.7 / 13.4 A RMS |
|
Peak
Current |
High
/ Low V range 22.2 / 44.5 A |
| Protection |
|
Adj.
Current limit |
Resolution
0.1 A RMS
Modes Const. Current or Const. Volt |
|
Over
Temperature |
- |
|
Over
Voltage |
- |
| Input |
|
Connection |
Rear
panel terminal block |
|
Line
Voltage |
2
wire + GND 103 - 127 V or 187 - 253 V V RMS |
|
Line
Current |
47
- 440 Hz |
|
Holdup
Time |
10
ms |
|
Isolation |
Input
to Chassis/Output 1350 / 2200 V |
|