 Optional
Accessories:
CT-10 Clamp-on CT
Rated 1-10Amps AC
Frequency response: 45Hz-3kHz
Jaw Opening: 0.47"
CT-150 Clamp-on CT
Rated 0.25-150 Amps AC.
Frequency response: 45Hz to 3kHz.
Jaw Opening: 0.47"
CT-300 Clamp-on CT
Rated 10-300 Amps AC.
Frequency response: 45Hz to 3kHz at stated accuracy.
Jaw Opening: 2.00"
CT-1000 Clamp-on CT
Rated 50-1000 Amps AC.
Frequency response: 30Hz to 3kHz at stated accuracy.
Jaw Opening: 2.17"
CT-3000 Clamp-on CT
Rated 100-3000 Amps AC.
Frequency response: 48Hz to 3kHz.
Jaw Opening: 2.56", bus bar 1.97" X 5.31" max.
Mainframe Options
- Harmonics Analysis
- Extended Memory
- Internal Modem
|
|
Energy Analyzer
- Motor Inrush Analysis
- Harmonic Analysis
- Removable Memory Cards
- Rated Schedule Analysis
- PC Analysis Software
Specifications
- Measured Parameters Voltage
* Channels: Three voltage channels with common return and one full-differential
channel.
* Range: AC 60 to 600 Volts RMS for channels A, B, C. 0 to 600 volts for channel D
- Current
* Channels: Four current digital channels
* Range: 10% to 200% full scale of CT; 2% to 100% full scale for channel D
- Digital
* Channels: Four digital channels
* Range: 12 to 48 volts DC
- Frequency
* Range: 20 to 450 Hz fundamental
Computed Parameters
- Demand: Average demand during interval in kW, kVA, kVAR.
- Energy: Cumulative energy used in kWH, kVAH, kVARH
- Power Factor
True PF and displacement PF
- Time Clock
- Memory: Non-Volatile Memory 512 kbytes standard
- Printer: High resolution graphics, thermal printer
- Display: 4.25" X 2.27" Liquid crystal
display
- Serial Ports: One 25-pin RS232D communication port, 300-9600
baud
- Relays: 4 output relays for external access, rated 120 VAC at
1A, 30VDC at 1 A
- Memory Card: PCMCIA/JEIDA compatible (Available separately)
- Trigger Conditions
A report can be initialized by:
* Limited crossing of any parameter
* Specified time (max. of 4 per day)
* End of demand interval
* Time interval (other than demand interval)
* End of billing period
* Upon request
|