AC Line Conditioner
- Input Voltage Range: 94 - 138
- Output:
- Power (VA): Cont.: 1000; Peak: 5000
- Voltage (VRMS): 115
- Frequency (Hz): 57 - 63
- Input/Output Isolation: 100 dB (60Hz)
- Output Distortion: 0.2% max for up to 10% input harmonic distortion
- Line Regulation: ± 0.025% for ± 10% input AC line variation
- Load Regulation: ± 0.025% for no load/full load full current into unity to zero
lagging or leading load
- Reduces 500V 10µsec transients by 1000:1
- Supplies peak currents 3.5 times RMS rating
- Temperature coefficient: 0.005% per °C
- Peak amplitude stability: ± 0.01% (cycle to cycle)
- Amplitude drift: ± 0.05% 24 hrs constant line, load and temperature
- Impulse settling time: less than 10µsec
|