Fluke 430 Series Three-Phase Power Quality Analyzers
The Fluke 434 and Fluke 433 three-phase
power quality analyzers help you locate, predict, prevent and troubleshoot
problems in power distribution systems. These easy-to-use handhelds are a
quality tool for any person who maintains or troubleshoots three phase
distribution. The new IEC standards for flicker and power quality are
built right in to take the guess work out of monitoring.
Features:
-
Records all your necessary values in a
three phase system.
-
Minimal setup required with intuitive
menus.
-
Highest safety rating in the industry.
-
Four voltage and four current channels.
-
Captures waveform data on all phases
simultaneously.
-
System-Monitor: Six power quality
parameters on one dashboard
-
Automatic Transient display: Never miss
an event.
-
Auto Trend: Dont waste time setting
up recordings.
-
Rugged, handheld recorder.
-
Seven hours operating time per charge
on NiMH battery pack.
-
Transfer data files to your PC for
reporting and analysis using FlukeView® software.
| Specifications: |
| Input
characteristics |
| Voltage
inputs |
| Number
of inputs |
4
(3 phases + neutral) |
| Maximum
input voltage |
1000
Vrms |
| Maximum
peak voltage |
6
kV |
| Input
impedance |
4
MW / 5 pF |
| Bandwidth |
9
kHz, up to 100 kHz for transient display |
| Scaling |
1:1,
10:1, 100:1, 1000:1 and variable |
| Current
inputs |
| Number
of inputs |
4
(3 phases + neutral) |
| Type |
Clamp
on current transformer with mV output |
| Range |
1 to 400 Arms with included clamps
(I400S)
0.1 to 3000 Arms with optional clamps |
| Input
impedance |
50
kW |
| Bandwidth |
9
kHz |
| Scaling |
0.1,
1, 10, 100, 1000 mV/A and variable |
| Nominal
frequency |
40
to 70 Hz |
| Sampling
system |
| Resolution |
16
bit analog to digital converter on 8 channels |
| Maximum
sampling speed |
200
kS/s on each channel simultaneously |
| RMS
sampling |
5000
samples on 10/122 cycles according IEC 61000-4-30 |
| PLL
synchronization |
4096
samples on 10/122 cycles according IEC 61000-4-7 |
| Display
modes |
| Waveform
display |
Available in Scope and Transient mode
Captures 8 waveforms simultaneously
Display update rate 5 x per second
Up to 10/12 times horizontal zoom
Cursors: Single vertical line showing min, max, avg reading at
cursor position |
| Phasor |
Shows real time phasor diagram
Available in Scope and Unbalance mode
Display update rate 5 x per second |
| Matrix
readings |
Available in Volts/Amps/Hertz,
Harmonics, Power & Energy, Flicker and Unbalance mode |
| AutoTrend
graph |
Available in Volts/Amps/Hertz, Dips
& Swells, Harmonics, Po& Energy, Flicker, Unbalance,
Inrush and Monitor mode
Cursors: single vertical line showing with min, max, avg reading at
cursor position |
| Bargraph |
Available
in Harmonics and Monitor mode |
| Eventlist |
Available
in Dips & Swells and Monitor mode |
also see the AEMC