Velonex 510 Surge Transient Generator
- Surge Withstand Capability (SWC) wave shape and characteristic that meet and
exceed those required by the IEEE/ANSI standard C37.90a-1978 (formerly IEEE standard
472-1974)
- Monitor Output: A low-level 1000:1 attenuated output referenced to ground is
provided for scope monitoring
- Trigger Output: A front panel scope trigger output signal is provided
- Output Voltage: (Open Circuit; crest of 1st Half Cycle Peak) Variable by front
panel control from 1.5kV (<300V with a more rapid envelope decay) to 2.5kV
- Source Impedance: Selectable 100 ohms, 150 ohms, 300 ohms, 600 ohms, 1200 ohms
- Test Burst Rep Rate: Manual one-shot, plus continuously variable from < 20
bursts per second to > 120 bursts per second, plus 50 or 60 Hz synchronized with power
line, plus 100 or 120 Hz synchronized with power line. Phase or burst is adjustable
through > 320° with respect to power line frequency
- Test Duration: Continuously adjustable from < 2 seconds to > 10 seconds
- Isolation Networks
* Maximum Current: 10ARMS per phase
* Number of AC Lines: any number up to and including four
* Maximum Voltage: 700VRMS between input lines and
case
* Electrical Connections (Power Line-In & EUT): Barrier strips with lugs for
connection between power in and DUT (EUT) are provided on rear of instruments
|