| Voltage (V) |
| Range (Auto or Manual) |
0.5V to 2000Vpk |
| (12 ranges 1-2-5 sequence) |
(1000V rms) |
| Scaling Factors |
1.0000 to 99999 |
| Computation |
True rms or rectified mean |
| Crest Factor |
Up to 20 |
| Frequency Range |
DC and 0.1Hz to 200Hz |
Accuracy 23° ± 5°C
0.2V 1000Vrms |
45 - 450Hz: |
±0 .1% rdg ±0 .1% range ± 20mV |
| 1.Hz-200kHz: |
±0 .2% rdg ±0 .1% range 0.05%/kHz |
| Effect of common |
1000Vrms 60Hz: |
Less than 2OmV |
| Mode Voltage |
100Vrms 100kHz: |
Less than 200mV |
| Maximum Input |
Continuous: |
2000Vpk |
| 1 second: |
5000Vpk |
| Input Impedance |
1 MΩ on all ranges at 15pF |
| Current (A) |
Range (auto or manual)
(12 ranges 1-2-5 sequences) |
INT: |
0 .05A to 200Apk (30A rms) |
| EXT: |
6 .25mV to 2.5Vpk (1 .5Vrms) |
| Scaling Factor |
INT: |
1 .0000 to 99999 |
| EXT: |
8OmA/mV to 80000A/mV |
| Computation |
True rms or rectified mean |
| Crest Factor |
Up to 20 |
| Frequency Range |
DC and 0.1Hz to 200Hz |
Accuracy 23° ± 5°C
20mA to 30Arms |
45 - 450Hz: |
±0 .1% rdg ±0.1% range ± 1mA |
| 0.lHz-200kHz: |
±0.2% rdg ±0.1%
range+0.05%/kHz ±1 mA |
| Effect of common |
1000Vrms 60Hz: |
Less than 20mA |
| Mode Voltage |
100Vrms 100kHz: |
Less than 200mA |
| Maximum Input |
Continuous: |
30Arms (must be limited by external fuses or CT's) |
| Input Impedance |
1 second: |
1000Apk |
| INT: |
0.0125Ω on all ranges |
| EXT: |
1 MΩ on all ranges at 15pF |
| Power (W) |
| Ranges (auto or manual) (144 ranges corresponding to V & A) |
25mW to 400kW pk (with scaling to 100,000MW) |
* please consult your sales representative about the availability of the single and three phase models