Digital AC Meter - 3 Phase, 4 Wire
Specifications
- Rated Input
* Voltage Ranges: 100V / 150V / 300V / 600V
* Current Ranges: 2A / 5A / 10A / 20A
* Wattage: 200W to 12kW (single phase); 600W to 36 kW (3~, 4 wire)
- Accuracy: ± (0.25% of reading + 0.05% of range), 50 to 60 Hz.
* Volts, Amps, Watts: ± (0.5% of reading + 0.1% of range), 25Hz to 2kHz
* Volts and Amps: ± (0.5% of reading + 0.1% of range), 40Hz to 1.2kHz Watts
- Crest Factor
* Voltage: up to 2 (1,000V peak max)
* Current: up to 3 (50A peak max)
- Impedance and Burden: Approx. 50kW on 100V, 100kW on 150V, 400kW on 300V, 1.5MW on 600V, range. Approx. 0.1VA on 2A, 0.4VA on 5A, 1VA on 10A,
2VA on 20A range
- Power Factor Error: Usable from zero power factor to unity, additional error;
less than ±0.25% (single phase), ±0.5% (3~, 4W) of reading
- Analog Output: 5VDC, load current 1mA (max.)
|