AEMC SDL-A303 Sentinel Current Data Logger
This Sentinel Current Data Logger Model is a small, portable, three channel recording device. Line tracking is performed such that 64 samples over one line cycle are taken. Frequency tracking is performed over the range ±3 Hz around the nominal line frequency (50 or 60 Hz). Power Quantity and Power Quality measurements are calculated from these 64 samples for all input channels.
The Sentinel records RMS for each of the inputs at a rate of up to four times per second. Measurements for each channel are taken sequentially. Meaning that while the instrument is taking samples on one channel the other channels are ignored. The measurement process is performed on a single line cycle. This means that the inputs and line cycles are ignored between measurement intervals.
General Specifications
- Recording Storage Period: 250ms to 12 hours
- Recording Session Length: Programmable from 1 minute to 8 weeks.
- Total Memory: Record 480,000 events
- Storage Technique: Start/Stop, FIFO, Extended Recording Mode
- Input: Three current input using integrally wired flexible AmpFlex sensors. 64 samples/cycle are taken to calculate TRMS value for each input.
Interface
- Output: USB 2.0 Compliant
- Isolation: Optically isolated, 5.5kVrms max.
- Speed: 115.2 kbps
Electrical
- Range: 5 to 1000A
- Display Resolution: 0.1A
- Accuracy:
- ±(1.0% of Reading + 1.0A) from 100 to 1000A.
- ±(1.0% of Reading + 1.2A) from 5 to 100A.
|