Accessories:
- 5 foot sense control leads
- 5 foot high current leads (4/0 and 4 Ga)
- 5 foot low current leads (10 Ga)
|
|
Phenix HC-2 Portable High Current Test Set / Circuit Breaker Test Set
Specifications:
- Input: 120 Volts or 220 Volts, 50 or 60 Hz preset
- Output:
- 0-70 Volts at 25 amperes
- 0-14 Volts at 125 amperes
- 0-7 Volts at 250 amperes
- 0-3.5 Volts at 500 amperes
- Overload: Short duration overloads are possible on each tap. The
test set is capable of up to 2000 amps, depending on the impedance of
the test circuit.
- Duty Cycle:
- Continuous at 100%
- 5 minutes ON/15 minutes OFF at 200%
- 1 minute ON/5 minutes OFF at 300%
- 30 seconds ON/5 minutes OFF at 400%
- Instrumentation:
- Currentmeter: 3.5 digit LCD
- Ranges: 0-1.999/19.99/199.9/1999 amperes
- Accuracy: ±.5%
- Timer: 6 digit LCD, in cycles or seconds
- Ranges: 0-999999 cycles or 0-9999.99 seconds
- Accuracy: ±.1% reading
|