Accessories
- 5 foot sense control leads
- 5 foot high current leads (4/0 and 4 Ga)
- 5 foot low current leads (10 Ga)
|
|
Portable High Current Test Set / Circuit Breaker Test Set
The HC-2 High Current Test Set is built for field and shop use. This unit combines a variable high current ouput with appropriate controls and instrumentation for testing thermal, magnetic, and solid-state motor overload relays as well as molded-case circuit breakers and ground fault trip devices. The HC-2 can also be used in many other applications requiring a high current source.
Specifications
| Input |
120 Volts or 220 Volts, 50 or 60 Hz preset |
| Output |
0-70 Volts at 25 amperes |
| 0-14 Volts at 125 amperes |
| 0-7 Volts at 250 amperes |
| 0-3.5 Volts at 500 amperes |
| Overload |
Short duration overloads are possible on each tap. The test set is capable of up to 2000 amps, depending on the impedance of the test circuit |
| Duty Cycle |
Continuous at 100% |
| 5 minutes ON/15 minutes OFF at 200% |
| 1 minute ON/5 minutes OFF at 300% |
| 30 seconds ON/5 minutes OFF at 400% |
| Instrumentation |
Current meter: |
3.5 digit LCD |
| Ranges: |
0-1.999/19.99/199.9/1999 amperes |
| Accuracy: |
±.5% |
| Timer: |
6 digit LCD, in cycles or seconds |
| Ranges: |
0-999999 cycles or 0-9999.99 seconds |
| Accuracy: |
±.1% reading |
|