Optional Probes and Accessories
- AEMC 193-24: 10-6500A 24" AmpFlex Current Probe
- AEMC 193-36: 10-6500A 36" AmpFlex Current Probe
- AEMC MN93: 100mA-240A 0.78" Current Probe
- AEMC SR193: 3-1200A 2.5" Current Probe
- AEMC MR193: 10-1000A AC/10-1400A DC 1.6"
- AEMC MN193: 5mA-6A AC/ 100mA-120A AC 0.78"
|
|
AEMC 3945 Three-Phase Power Quality Analyzer PowerPadT
AEMC’s PowerPad Model 3945 full color
graphical display lets you see and analyze volts, amps and harmonic
content in real time and take pictures to document and analyze clearly.
Its high speed sample rate, at 256 samples per cycle, provides excellent
fidelity in reproducing waveforms and capturing transients that happen as
fast as 62.5µs.
The AEMC 3945 PowerPad’s 4MB of memory is
conveniently partitioned to let you store four different types of data,
synchronized or independent of each other. You can store up to 12 screen
snapshots, up to 50 captured transients that contain four cycles for each
active input, and 4096 alarm events. You can also record trend data for
days, weeks or even months.
Features:
- True RMS single-, two- and three-phase measurements at 256 samples/cycle, plus DC
- Real-time color waveforms
- Easy-to-use on-screen setup
- Automatic current probe recognition and
scaling
- True RMS voltage and current
measurement
- Measures DC volts, amps and power
- Display and capture voltage, current
and power harmonics to 50th order, including
direction, in real time
- Capture transients down to 1/256th of a
cycle
- Phasor diagram display
- Peak voltage and current
- Nominal frequency from 40 to 70Hz
- VA, VAR and W per phase and total
- kVAh, VARh and kWh per phase and total
- Neutral current display for three-phase
- Crest factors for current and voltage
- Transformer K-factor display
- Power Factor, displacement PF display
- Captures up to 50 transients
- Short-term flicker display
- Phase unbalance (current and voltage)
- Harmonic Distortion (total and
individual) from 1st to 50th
- Alarms, surges and sags
- Records date and characteristics of
disturbances
- Immediate printout directly to a
printer
- Screen snapshot function captures
waveforms or other information on the display
- Optically isolated RS-23 communication
port
- Includes DataView®Professional
software for data storage, analysis and report
generation
- EN 61010, 600V Cat. III
Applications:
- Verification of power distribution
circuits
- Measurement and recording of power
system quality (kW, VA, VAR)
- Energy metering (kVAh, VARh, kWh)
- In plant troubleshooting of power
distribution panels and individual machinery
- Monitor pad mount transformers
- Determine harmonic problems originating
from source or load
- Monitor phase unbalances
- Determine transformer K-factor
- And much, much more
| Electrical
Specifications: |
| Sampling
Frequency |
256
samples per cycle |
| Data
Storage |
4MB
partitioned for waveforms, transients, alarms and trend recording |
| Voltage
(TRMS) |
Phase-to-Phase:
830V Phase-to-Neutral: 480V |
| Current
(TRMS) |
MN
Clamp: 0 to 6A/120A or 0 to 240A
MR Clamp: 0 to 1200AAC, 0 to 1400ADC |
SR
Clamp: 0 to 1200A
AmpFlex™: 0 to 6500A |
| MEASUREMENT |
RANGE |
RESOLUTION |
ACCURACY |
| Single-Phase
RMS Voltages |
6
to 480V |
0.1V |
±0.5%
± 2cts |
| Phase-to-Phase
RMS Voltages |
10
to 830V |
0.1V |
±0.5%
± 2cts |
| Single-Phase
Peak Voltages |
6
to 680V |
1V |
±(1%
+ 5cts) |
| Phase-to-Phase
Peak Voltages |
10
to 1360V |
1V |
±(1%
+ 5cts) |
| Frequency
(Hz) |
40
to 69Hz |
0.01Hz |
±0.01Hz |
| DC
Voltage Component |
6
to 650V |
0.1V |
±1%
± 2cts |
Current Probes (Arms)
MN Clamp
SR Clamp
AmpFlex™ Probe |
0 to 240A
0 to 1200A
10 to 6500A |
0.1A
0.1A; 1A ≥ 1000A
0.1A; 1A ≥ 1000A |
±(0.5% + 2cts)
±(0.5% + 2cts)
±(0.5% + 1A) |
| Active
(Real) Power (kW) |
0
to 9999kW |
4
digits (10,000ct) |
±1%
± 1ct @ PF ≥0.8 |
| Reactive
Power (kVAR) |
0
to 9999kVAR |
4
digits (10,000ct) |
±1%
± 1ct @ PF ≥ 0.8 |
| Apparent
Power (kVA) |
0
to 9999kVA |
4
digits (10,000ct) |
±1%
± 1ct |
| Power
Factor (PF & DPF) |
-1.000
to 1.000 |
0.001 |
±(1.5%
+ 0.01) |
| Active
Energy (kWh) |
0
to 9999MWh |
4
digits (10,000ct) |
±1%
± 1ct @ PF ≥ 0.8 |
| Reactive
Energy (kVARh) |
0
to 9999MVARh |
4
digits (10,000ct) |
±1%
± 1ct @ PF ≥ 0.8 |
| Apparent
Energy (kVAh) |
0
to 9999MVAh |
4
digits (10,000ct) |
±1%
± 1ct |
| Unbalance
(V & A) |
0
to 100% |
0.1% |
±1%
± 1ct |
| Phase
Angle (V–A, A–A, V–V) |
-179°
to +180° |
1° |
±2°
± 1ct |
Harmonics
(1st to 50th)
F = 40 to 69Hz
(V ≥ 50V, A > Inom/100) |
0
to 999% |
0.1% |
±1%
+ 5cts |
| Total
Harmonic Distortion (V & A) |
0
to 999% |
0.1% |
±1%
+ 5cts |
| K-factor
(Akf) |
1
to 99.99 |
0.01 |
±5%
± 1ct |
| Flicker
(PST) |
0.00
to 9.99 |
0.01 |
- |
| Power
Source |
9.6V NiMH rechargeable battery pack
AC supply: 110/230VAC ±20% (50/60Hz) |
|