Input |
100 to 265 V, 1Ø, 50 or 60 Hz, 15 A max. |
Output |
Continuously variable in four ranges: |
0 to 40 V at 2.0 A max (5 minute on 15 minute off)
0 to 40 V at 5 A max for burden test
0 to 40 V at 5 A max for burden test
0 to 40 V at 5 A max for burden test
0 to 40 V at 5 A max for burden test
|
Instrumentation |
Voltmeters |
Output 4½ digit, auto ranging |
Resolution |
0.0000 to 1.9999/19.999/199.99/1999.9 |
Ranges: |
0 to 40/160/800/1600 V |
Accuracy: |
±0.5% of reading, and ±.5% range typical ±1% of reading and ±1 V maximum |
Input 4½ digit, auto-ranging |
Ranges: |
0 to 2/600 |
Resolution: |
0.0000 to 1.9999/19.999/199.99/600 V |
Accuracy |
2 V Range: |
±0.5% of reading and ±0.25% range |
600 V Range: |
±0.5% of reading and ±0.5% range |
Ammeter 4½ |
Range: |
0.0000 to 1.0000A/5.000 |
Accuracy: |
±0.85% of reading and ±1 LSD |
Phase Angle 3 digits |
Range: |
0 to 360 degrees |
Accuracy: |
±1 degree* |
Ratio |
Range |
Accuracy |
0.8 to 5000 |
±0.4% typical |
|
±0.8% maximum |
Ratio Test Frequency |
55Hz internally generated providing a universal 50/60Hz test set |
Winding Resistance |
Measuring Range: |
.01Ω to 99.9Ω |
Accuracy: |
<9.99Ω ±3% of reading ±2 digits < 99.9Ω ±5% of reading ±2 digits |
Insulation Test |
Test Voltage: |
1000 VDC, 500 VDC |
Measuring Range: |
10kΩ – 999MΩ |
Short Circuit Current: |
1.5mA nominal |
Test Current on Load: |
1mA at min. pass values of insulation (as specified in BS7671, HD 384 and IEC 364) |
Accuracy: |
±3%, ±2 digits up to 10MΩ
±5%, up to 100MΩ
±30% up to full scale |
Communication Interfaces |
Ethernet/USB |
Environment |
Operating: |
-10° C to 40° C |
Storage: |
-30° C to 70° C |
Weight |
47.6 lb (21.6 kg) |