Available types |
Max burst amplitude |
Max burst frequency |
Coupling phase |
Network current |
Front panel key-pad/display |
NSG 2025-4 |
4.4 kV |
1 MHz |
3 |
30A |
yes |
NSG 2025-7 |
8 kV |
500 kHz |
1 |
30A |
yes |
NSG 2025-8 |
8 kV |
500 kHz |
3 |
30A |
yes |
|
Unit Power |
100 - 115 V and 220 - 240 V, 50 - 60 Hz |
Pulse Amplitude |
200 V to 4.5 or 8 kV (open circuit) adjustable in steps of 20 V |
Polarity |
positive or negative, selectable |
Rise Time |
5ns ±20% (50 W, 10 - 90%) |
Pulse Width |
50ns ±30% (50 W and 1 W), 100ns ±50% open circuit |
Pulses Per Packet |
1 to 150 pulses |
Burst Duration |
Pulses per packet / burst frequency, (15ms burst duration as per IEC 1000-4-4 up to 10 kHz) |
Burst Repetition |
100ms to 10s ±2ms or 2% |
Impedance |
50 W ±20% |
Coupling Network |
1-phase or 3-phase |
EUT Supply |
Switched by remote control, 24 to 500 Vac, 50 - 60 Hz |
Coupling Modes |
Line to reference ground (IEC 1000-4-4), selected lines together to reference ground, all lines to reference ground (common mode) |
Phase Angle |
Asynchronous/synchronous 0 - 360° ±2° |
Coupling Capacitance |
33 nF |
Decouple Attenuation |
>20 dB |
Cross Talk Attenuation |
>30 dB |