Eagle Eye LB-Series SMART DC Load Banks

Rent Eagle Eye LB-Series SMART DC Load Banks
Enlarge Image
Request Quote Print Page
Datasheet
The Eagle Eye LB-Series SMART DC Load Banks are designed for discharge testing, battery capacity testing, acceptance testing, battery maintenance and other testing for DC power with a load. The LB-Series load banks are portable, economic, easy-to-use and come complete with DataView Software for data management and analysis. With over 35 standard models, the LB-Series is used in a variety of industries including utilities, telecommunications, UPS, motive power/forklifts, transportation, CATV and many more. Custom Solutions are available. Eagle Eye load banks are designed to make discharge testing convenient and easy for any application.

Features:

  • SMART Load Banks with system monitoring and cell monitoring
  • Powerful management software for data analyzing and report building
  • Rugged, compact and portable units
  • PTC Ceramic resistor for safe discharging
  • Four settings for auto shut-down of discharge: discharge time, discharged capacity, cell cut-off voltage and total cut-off voltage
  • Parallel connection of two units for mass discharge testing
  • Thermal cut-off and automatic overload protection
  • Safe circuits avoid damage to battery when testing

Specifications:

Cell Voltage Standard DAC: 1.2V*, 2V, 6V, 12V / Optional: Custom DAC configurations available upon request
Discharge Current Range Single Load: 12 – 600A / Parallel Load: 24 – 1200A
Discharge Voltage Range Range: 10 – 576V (Max)
Voltage Steps: 12V, 24V, 36V, 48V, 80V, 125V, 240V, 380V, 480V
Accuracy Discharge Current: 1% / Voltage: 0.5% – 0.8%
Resolution Discharge Current: 0.1 A or 0.5% / Voltage: 0.001 V
Sampling Interval 5 seconds – 1 minute
Data Transfer USB, Wireless (466 MHz)
Display Backlit LCD
Operating Environment 0 – 40 °C (32 – 104 °F)
Power Requirements 110/220 VAC 50/60 Hz / DC (from connected batteries)