Hipotronics TDR 1170 Time Domain Reflectometer

Rent Hipotronics TDR 1170 Time Domain Reflectometer
Enlarge Image
Hipotronics TDR 1170
Request Quote Print Page
Datasheet

The unique features and new technology used in the Hipotronics TDR 1170 Time Domain Reflectometer make it the most flexible and easiest to use instrument available for advanced cable fault location. The TDR 1170 features an automatic configuration, which can be modified as necessary. All cable fault data can be stored and retrieved at any time, ensuring time savings, consistency and accuracy from one crew to the next.
 

The digital Hipotronics Time Domain Reflectometer will locate and identify short circuit (bolted) faults, low resistance shunt faults, open circuits, high resistance series faults, wet sections, splices, transformers, cable transitions, and concentric neutral corrosion. To locate high resistance, intermittent and flashover faults, the TDR 1170 is designed to measure in the digital arc reflection, current impulse, voltage decay, and all differential fault locating modes. The selection of fault location method allows the operator to select the method which they are most familiar with or the method that is most appropriate for the type of cable and type of fault that is encountered.
 

The TDR 1170 requires a high voltage coupler to interface to a cable fault locator (thumper). The cable fault locator then provides the voltage and current to enable the TDR 1170 to quickly and definitively locate cable faults.
 

Features:

  • Digital High Voltage TDR
  • 5 Methods of Fault Location
    • Arc Reflection
    • Impulse Current
    • Voltage Decay
    • Differential Methods
    • Low Voltage
  • Color LCD Screen
  • PC Software
  • SVGA Output for External Monitor

 

Benefits:

  • Pre-Locate Faults
  • Diagnose Cable Faults
  • Easy to Use
  • Compatible with Common "Thumpers"
  • Provides Long-Term Storage and Evaluation
  • Cable System Signature Mapping
  • Reduce Outage Time
  • Reduce Cable Damage
  • Simplified Operator Training

 

Specifications:

Input Voltage: 90 to 250 V AC, 50/60Hz
Accuracy: < ± 1% of cable length
Measuring Range: 1 ft. to 160,000 ft.
Units of Measure: Feet, Yards, Meters
Trigger Delay: 1 to 30ms
Setup: 16 setup options
VP Range: 98ft./μs to 492ft./μs
Pulse Amplitude: 25 V into 50W
Pulse Width: 50ns to 10μs
Sample Rate: 12.5 to 30ms
Memory Modes: 32 sets of 1 or 3 phase
RS232 Port: Download traces to PC
Weight 18lbs
Dimensions 19" x 10.5" x 7" (48 x 26 x 18 cm)