Manta MTS-1010 Multi-Function Power Meter

Rent Manta MTS-1010 Multi-Function Power Meter
Enlarge Image
Manta Test Systems MTS-1010
Request Quote Print Page

The Manta MTS-1010 Multi-Function Power Meter is a  portable, microprocessor based meter developed specifically for power related applications in the relay, metering and instrumentation & control departments. The MTS-1010 can used to verify metering and relaying circuits for accuracy, polarity and phase. It can also be used to do timing checks or monitor the outputs of unmetered test equipment. When used in conjunction with the Manta Test Systems MTS-1200 3 Channel Voltage/Current Source (and optionally the MTS-1300 3 Phase Voltage Source) it can form the basis for an economical and capable protective relay test set.
 

Features:

  • Ten simultaneous measurements
  • Very responsive controls and displays
  • Lightweight, easy to use
  • High ampacity current inputs
  • True RMS, fully autoranging
  • Phasor display of AC quantities
  • Optimized for relay and meter applications
  • High intensity LED displays
 

Specifications:

Power Supply
  • 120 VAC/60 Hz version: 100-130VAC at 50-70Hz
  • 240 VAC/50/60 Hz version: 220-260VAC at 47-70Hz
  • With option 04A: 12VDC
 
Frequency measurement
  • Ranges: 8.00 - 99.99Hz (low scale), 8.0-500.0 Hz (high scale)
  • Resolution:
    • 0.001 Hz for 8.000-9.999 Hz input
    • 0.01 Hz for 10.00-99.99 Hz input
    • 0.1 Hz for 100.0-650.0Hz input
  • Accuracy: +/-0.01 Hz (low scale), +/- 0.1 Hz (high scale)
  • Measurement speed:
  • Measurement speed is dependent upon input frequency
    • for 60 Hz input: 2 readings/sec (normal mode), 7.5 readings/sec (high speed mode)
    • for 50 Hz input: 1.6 readings/sec (normal mode), 6.3 readings/sec (high speed mode)
 
AC/DC Voltage measurement
  • True RMS responding, DC coupled
  • Available on channel A and/or B
  • Accuracy: +/-0.5% of reading +/- 0.2% of scale
  • Ranges: 0-19.99/ 199.9/ 1999V, autoranging at 19.99, 199.9V
  • Maximum input: 600VAC continuous
  • Resolution: 0.01V (lowest scale)
  • Input impedance: 2 megohms
  • Measurement speed: 3 readings/sec (normal mode), 30 readings/sec (high speed mode)
 
AC Current measurement
  • True RMS responding, AC coupled
  • Available on channel A and/or B
  • Accuracy: +/-0.5% of reading +/- 0.2% of scale
  • Ranges: 0-1.999/ 19.99/ 199.9A, autoranging at 1.999, 19,99A
  • Maximum input: 35A continuous, 125A for 5 seconds
  • Resolution: 0.001A (lowest scale)
  • Measurement speed: 3 readings/sec (normal mode), 30 readings/sec (high speed mode)