T&R DVS3 Relay Test System

Rent T&R DVS3 Relay Test System
Enlarge Image
Request Quote Print Page
Datasheet

The DVS3 mk2 is the new smaller, lighter, higher power version of the T&R DVS3, offering three times the output power of the original DVS3. The exceptionally easy to understand user interface of the DVS3 is retained, allowing simple testing of complex voltage and loss of mains protection systems. Equally at home in a commissioning, maintenance, or laboratory environment, the DVS3 mk2 is a truly flexible system. The DVS3 mk2 has been designed using the latest digital technology to generate a highly stable and accurate output with very low distortion. Each phase output is individually adjustable for voltage and phase angle. In addition, full control of frequency is available. Step changes of any quantity may be generated with automatic timing of the response of the relay under test.
 

Features:
 

  • 3-f Voltage output from 1-f supply
  • 0-133V f-N output voltage 0-266V/292V f-N with optional VT box
  • 45VA/phase maximum output
  • Variable Frequency 40-999.9Hz
  • Phase shift ±180.0°
  • Multi-function timing system
  • Ideally suited to testing G59 schemes
  • Step change of phase and df/dt
  • Large back-lit liquid crystal display
  • Compact and lightweight
  • Automatic mains voltage selection

Specifications:


Voltage: 0-133Vac phase-neutral
0-230Vac phase-phase
Current (Continuous): 200mA at 133V, 120mA at 0.1V
Current (5min on/ 15min off): 335mA at 133V, 200mA at 0.1V
Voltage Resolution: 0.1V phase-neutral
Phase Rotation: ±180º
Voltage Accuracy: ±0.3%rdg+3d