Teseq ProfLine 2100 Harmonics and Flicker Measuring System

Teseq ProLine 2100 Harmonics and Flicker Measuring System
Enlarge Image
Request Quote Print Page
Datasheet Brochure
The ProfLine 2100 system is a complete and cost effective harmonics and flicker measurement test system to the latest IEC/EN standards. The programmable power generation capability of up to 45 kVA (90 kVA and 145 kVA sources comprise multiple 45 kVA units) provides more than ample power to cater for a wide range of Equipment Under Test (EUT). In addition to harmonics and flicker testing capability the AC/DC power source used in the system is capable of testing to a wide range of power quality immunity tests. In short, this system is a one stop power quality testing station that will help you meet your EMC responsibilities for compliance testing.

The ProfLine 2100 system comes in two models:
  • ProfLine 2100-1 which is a single phase harmonics & flicker measuring system
  • ProfLine 2100-3 which is a three phase harmonics & flicker measuring system.
 

Features:

  • Cost effective, complete and compliant
  • Variable output power configuration from 3 kVA to 45 kVA (90 and 145 kVA sources comprise multiple 45 kVA units)
  • Easily upgradeable PC based
  • Use existing power sources or mains measurement system
  • Immunity test system
  • Key 'Equipment Under Test' electrical parameters updated continuously
  • User selectable test parameters and data display option
  • Test report customization capability
 

Specifications:

 
ProfLine 2100-1
ProfLine 2100-3
System contents
CCN 1000-1 1-phase
coupling unit
DAQ card
Interface cable
WIN 2100 test software
CCN 1000-3 1-phase
coupling unit
DAQ card
Interface cable
WIN 2100 test software
Coupling unit
   
Number of phases 1 3
Measurement channels 4 12
EUT connector: Front panel CEE 77 None
EUT connector: Rear panel Terminal block Terminal block
Max. voltage: Front panel 240 Vac N/A
Max. current: Front panel 16 Arms N/A
Max. voltage: Rear panel 300 Vac 480 Vac
Max. current: Rear panel 40 Arms/Ph.
(200 A Pk for 10 ms)
40 Arms/Ph.
(200 A Pk for 10 ms)
Supply power: Voltage 115/230 Vac +/- 10% 115/230 Vac +/- 10%
Supply power: Current <0.5 A <0.7 A
Supply power: Frequency 50/60 Hz 50/60 Hz
DAQ card and cable
   
Interface PCI PCI
Size Standard height Standard height
Resolution 16 bit 16 bit
Speed 250 kSamples/s 1.25 MSamples/s
Cable length PC to CCN 2 m 2 m
 

Applications and Standards:

Harmonics standard:
IEC 61000-3-2 < 16 A per phase
IEC 61000-3-12 > 16 to 75 A per phase
 
Flicker standard:
IEC 61000-3-3 < 16 A per phase
IEC 61000-3-11 < 75 A per phase
 
Voltage Dip, interruption & variation:
IEC 61000-4-11 < 16 A per phase
IEC 61000-4-34 > 16 A per phase
 
Other immunity tests:
IEC 61000-4-8 Power line magnetic field
IEC 61000-4-13 Immunity to harmonics & inter-harmonics
IEC 61000-4-14 Repetitive voltage variations
IEC 61000-4-17 Ripple on DC input power ports
IEC 61000-4-27 Voltage & Phase unbalance immunity
IEC 61000-4-28 Frequency variations
IEC 61000-4-29 DC dips, variation and short interruption