Teseq ProfLine 2100 Harmonics and Flicker Measuring System

Teseq ProLine 2100 Harmonics and Flicker Measuring System
Enlarge Image
Teseq (Schaffner) ProfLine 2100
Request Quote Print Page
Datasheet Brochure
The ProfLine 2100 system is a complete and cost effective harmonics and flicker measurement test system to the latest IEC/EN standards. The programmable power generation capability of up to 45 kVA (90 kVA and 145 kVA sources comprise multiple 45 kVA units) provides more than ample power to cater for a wide range of Equipment Under Test (EUT). In addition to harmonics and flicker testing capability the AC/DC power source used in the system is capable of testing to a wide range of power quality immunity tests. In short, this system is a one stop power quality testing station that will help you meet your EMC responsibilities for compliance testing.

The ProfLine 2100 system comes in two models:
  • ProfLine 2100-1 which is a single phase harmonics & flicker measuring system
  • ProfLine 2100-3 which is a three phase harmonics & flicker measuring system.
 

Features:

  • Cost effective, complete and compliant
  • Variable output power configuration from 3 kVA to 45 kVA (90 and 145 kVA sources comprise multiple 45 kVA units)
  • Easily upgradeable PC based
  • Use existing power sources or mains measurement system
  • Immunity test system
  • Key 'Equipment Under Test' electrical parameters updated continuously
  • User selectable test parameters and data display option
  • Test report customization capability
 

Specifications:

 
ProfLine 2100-1
ProfLine 2100-3
System contents
CCN 1000-1 1-phase
coupling unit
DAQ card
Interface cable
WIN 2100 test software
CCN 1000-3 1-phase
coupling unit
DAQ card
Interface cable
WIN 2100 test software
Coupling unit
   
Number of phases 1 3
Measurement channels 4 12
EUT connector: Front panel CEE 77 None
EUT connector: Rear panel Terminal block Terminal block
Max. voltage: Front panel 240 Vac N/A
Max. current: Front panel 16 Arms N/A
Max. voltage: Rear panel 300 Vac 480 Vac
Max. current: Rear panel 40 Arms/Ph.
(200 A Pk for 10 ms)
40 Arms/Ph.
(200 A Pk for 10 ms)
Supply power: Voltage 115/230 Vac +/- 10% 115/230 Vac +/- 10%
Supply power: Current <0.5 A <0.7 A
Supply power: Frequency 50/60 Hz 50/60 Hz
DAQ card and cable
   
Interface PCI PCI
Size Standard height Standard height
Resolution 16 bit 16 bit
Speed 250 kSamples/s 1.25 MSamples/s
Cable length PC to CCN 2 m 2 m
 

Applications and Standards:

Harmonics standard:
IEC 61000-3-2 < 16 A per phase
IEC 61000-3-12 > 16 to 75 A per phase
 
Flicker standard:
IEC 61000-3-3 < 16 A per phase
IEC 61000-3-11 < 75 A per phase
 
Voltage Dip, interruption & variation:
IEC 61000-4-11 < 16 A per phase
IEC 61000-4-34 > 16 A per phase
 
Other immunity tests:
IEC 61000-4-8 Power line magnetic field
IEC 61000-4-13 Immunity to harmonics & inter-harmonics
IEC 61000-4-14 Repetitive voltage variations
IEC 61000-4-17 Ripple on DC input power ports
IEC 61000-4-27 Voltage & Phase unbalance immunity
IEC 61000-4-28 Frequency variations
IEC 61000-4-29 DC dips, variation and short interruption