Dimensions
(W x H x L) |
17 in x 12.5 in x 14 in
42.7 cm x 32 cm x 35.6 cm |
Weight |
60 lb.
27.2 kg |
Type |
Portable current transformer test set |
Input power |
100 ¬ 120 Vac
200 ¬ 240 Vac (factory pre-set)
50/60 Hz |
Measurement method |
ANSI/IEEE C57.12.90, IEC 60044-1 and ANSI/IEEE C57.13.1 |
Output test voltages |
0 ¬ 50 Vac @ 10A max
0 ¬ 300 Vac @ 10A max
0 ¬ 500 Vac @ 5A max |
Voltage reading range |
0 ¬ 2,200 Vac
Accuracy: ±1.0% of reading, ±1 volt |
Current reading range |
0 ¬ 10A
Accuracy: ±1.0% of reading, ±0.02A |
Current ratio range |
0.8 ¬ 999: 0.1%
1000 ¬ 1999: 0.3%
2000 ¬ 5000: 1% |
Resistance reading range |
100 µΩ ¬ 10 Ω
Accuracy: 2% of reading, ±1 count, ±10 µΩ |