Output voltage |
0 - 30 volts |
Output current |
0 - 600 Amps |
60 Hz voltage ripple |
70 M vrms |
60 Hz current ripple |
1.4 A rms |
AC input |
460 VAC ± 10% 30 60 Hz
440 to 480 VAC
Phase-to-phase balance requirements ±2% is required for ripple specification |
Regulation |
Effects of line and load variations on output voltage or current are within 0.1% |
Stability |
Output voltage and current remain within ±0.05% for 8 hours |
Transient response |
Output variations, caused by line variations of 10%
Load variations between 50% & 100% of rated limits
Typically recover to within 1% of its final value within 200 MS |
Remote sensing |
Maintains regulation at load, compensating for IR drops in the power output leads |
Remote programming |
Resistance programming of constant-voltage or constant-current modes |
Operation temperature |
0°C to 50°C
Derate current linearity to 50% of table rating at 71°C ambient |
Storage temperature |
-40°C to +85°C |