Power Specifications: |
Output Voltage: |
0 to 12 kV ac |
Output Current: |
100 mA continuous at 10 kV 200 mA > 30 minutes at 10 kV
300 mA > 4 minutes at 10 kV |
Operating time period based on 50°C operating temperature. Longer durations at high currents will be realized at lower operating temperatures
|
Output Power: |
3 kVA |
Sinusoidal output signal internal generated independent of input supply, No loss in performance when used with portable generator
|
AC INput |
95-264 V AC 47 to 63 Hz
16 A max at 110 V,
16 A max at 110 V, |
Test Frequency: |
Range: |
45 to 70 Hz independent of input signal |
Resolution: |
0.1 Hz |
Accuracy: |
±1% of reading |
Test Voltage: |
Range: |
25 V to 12 kV |
Resolution: |
1 V |
Accuracy: |
±1% of reading, ±1 V |
Test Current: |
Range: |
0 to 5.0 A |
Resolution: |
0.1 μA |
Accuracy: |
±1% of reading, ±1 μA |
Capacitance: |
Range: |
0 to 100 μF |
Resolution: |
0.01 pF |
Accuracy: |
± 0.5% of reading, ± 1 rF |
Inductance: |
Range: |
6 H to 10 MH |
Resolution: |
0.01 H |
Accuracy: |
± 0.5% of reading |
Watts: |
Range: |
0 to 2 kW, actual |
Resolution: |
0.5 mW |
Accuracy: |
± 2% of reading at 10 kV,
± 0.03% of VA, ±0.5 mW |
Dissipation Factor Range: |
%PF |
0 to ±100.00% |
PF |
0 to ±1.0000 |
% Tan δ |
0 to ±999.99% |
Tan δ |
0 to ±9.9999 |
mW/Var |
0 to ±9999.9 |
Resolution: |
0.01% / 0.0001 |
Accuracy: |
± 0.5% of reading, typical
&plismn;0.04% PF/Tan δ
± 0.0004 PF/Tan δ |
Temperature Measurement |
Range: |
-20 °C to +50 °C |
Resolution: |
0.1 °C |
Accuracy: |
±4 °C |
Instrument Dimensions |
10-1/4 in. H x 20 in. W x
25-1/4 in. D 26 cm H x
50.8 cm W x 64.1 cm D |
Weight |
95 lbs/45.5 kg |
High Voltage Cable: |
60 ft./18 mt (other lengths available as options) |