IEC
IEC 61000-3-13: Electromagnetic compatibility (EMC) Limits - Assessment of emission limits for...
Compliance Standards | EMC, Safety & Environmental Testing | ATEC
> IEC Standards
> IEC 61000-3-13 Testing
IEC 61000-3-13 Standard Overview
IEC 61000-3-13 provides guidance on principles which can be used as the basis for determining the requirements for the connection of unbalanced installations (i.e. three-phase installations causing voltage unbalance) to MV, HV and EHV public power systems (LV installations are covered in other IEC documents). For the purposes of this report, an unbalanced installation means a three-phase installation (which may be a load or a generator) that produces voltage unbalance on the system. The connection of single-phase installations is not specifically addressed, as the connection of such installations is under the control of the system operator or owner.
The general principles however may be adapted when considering the connection of single-phase installations. The primary objective is to provide guidance to system operators or owners on engineering practices, which will facilitate the provision of adequate service quality for all connected customers. In addressing installations, this document is not intended to replace equipment standards for emission limits. The report addresses the allocation of the capacity of the system to absorb disturbances. It does not address how to mitigate disturbances, nor does it address how the capacity of the system can be increased.
Since the guidelines outlined in this report are necessarily based on certain simplifying assumptions, there is no guarantee that this approach will always provide the optimum solution for all unbalanced load situations. The recommended approach should be used with flexibility and judgment as far as engineering is concerned, when applying the given assessment procedures in full or in part. The system operator or owner is responsible for specifying requirements for the connection of installations which may cause unbalance on the system. The disturbing installation is to be understood as the complete customer's installation (i.e. including balanced and unbalanced parts).
Problems related to unbalance fall into two basic categories:
1. Unbalanced installations that draw negative-sequence currents which produce negative-sequence voltages on the supply system. Examples of such installations include arc furnaces and traction loads (typically connected to the public network at HV), and three phase installations where the individual loads are not balanced (typically connected at MV and LV). Negative-sequence voltage superimposed onto the terminal voltage of rotating machines can produce additional heat losses. Negative-sequence voltage can also cause non-characteristic harmonics (typically positive-sequence 3rd harmonic) to be produced by power converters.
2. Unbalanced installations connected line-to-neutral can also draw zero-sequence currents which can be transferred or not into the supply system depending on the type of connection of the coupling transformer. The flow of zero-sequence currents in a grounded neutral system causes zero-sequence unbalance affecting line-to-neutral voltages. This is not normally controlled by setting emission limits, but rather by system design and maintenance. Ungrounded-neutral systems and phase-to-phase connected installations are not, however, affected by this kind of voltage unbalance. This report gives guidance only for the coordination of the negative-sequence type of voltage unbalance between different voltage levels in order to meet the compatibility levels at the point of utilisation. No compatibility levels are defined for zero-sequence type of voltage unbalance as this is often considered as being less relevant to the coordination of unbalance levels compared to the first type of voltage unbalance. However, for situations where a non-zero impedance exists between neutral and earth with the system still being effectively grounded (i.e., where the ratio between zero-sequence, X0 and positive sequence reactance X1 is 0 < X0/X1 = 3), this type of voltage unbalance can be of concern especially when the type of connection of the coupling transformer allows zero-sequence path to flow from MV to LV and vice-versa.
This Technical Report has the status of a basic EMC publication in accordance with IEC Guide 107.
The general principles however may be adapted when considering the connection of single-phase installations. The primary objective is to provide guidance to system operators or owners on engineering practices, which will facilitate the provision of adequate service quality for all connected customers. In addressing installations, this document is not intended to replace equipment standards for emission limits. The report addresses the allocation of the capacity of the system to absorb disturbances. It does not address how to mitigate disturbances, nor does it address how the capacity of the system can be increased.
Since the guidelines outlined in this report are necessarily based on certain simplifying assumptions, there is no guarantee that this approach will always provide the optimum solution for all unbalanced load situations. The recommended approach should be used with flexibility and judgment as far as engineering is concerned, when applying the given assessment procedures in full or in part. The system operator or owner is responsible for specifying requirements for the connection of installations which may cause unbalance on the system. The disturbing installation is to be understood as the complete customer's installation (i.e. including balanced and unbalanced parts).
Problems related to unbalance fall into two basic categories:
1. Unbalanced installations that draw negative-sequence currents which produce negative-sequence voltages on the supply system. Examples of such installations include arc furnaces and traction loads (typically connected to the public network at HV), and three phase installations where the individual loads are not balanced (typically connected at MV and LV). Negative-sequence voltage superimposed onto the terminal voltage of rotating machines can produce additional heat losses. Negative-sequence voltage can also cause non-characteristic harmonics (typically positive-sequence 3rd harmonic) to be produced by power converters.
2. Unbalanced installations connected line-to-neutral can also draw zero-sequence currents which can be transferred or not into the supply system depending on the type of connection of the coupling transformer. The flow of zero-sequence currents in a grounded neutral system causes zero-sequence unbalance affecting line-to-neutral voltages. This is not normally controlled by setting emission limits, but rather by system design and maintenance. Ungrounded-neutral systems and phase-to-phase connected installations are not, however, affected by this kind of voltage unbalance. This report gives guidance only for the coordination of the negative-sequence type of voltage unbalance between different voltage levels in order to meet the compatibility levels at the point of utilisation. No compatibility levels are defined for zero-sequence type of voltage unbalance as this is often considered as being less relevant to the coordination of unbalance levels compared to the first type of voltage unbalance. However, for situations where a non-zero impedance exists between neutral and earth with the system still being effectively grounded (i.e., where the ratio between zero-sequence, X0 and positive sequence reactance X1 is 0 < X0/X1 = 3), this type of voltage unbalance can be of concern especially when the type of connection of the coupling transformer allows zero-sequence path to flow from MV to LV and vice-versa.
This Technical Report has the status of a basic EMC publication in accordance with IEC Guide 107.
Related IEC Standards
Explore All Standards
IEC 60050-444 International Electrotechnical Vocabulary Part 444: Elementary Relays
IEC 60255: Electrical Relays
IEC 60270: Partial Discharge Measurements
IEC 60533: EMC Testing of Ships with Metallic Hulls
IEC 60601-1-2: Medical Electrical Equipment - Collateral standard: Electromagnetic compatibility...
IEC 61000-3-2: Limits - Limits for Harmonic Current Emissions (equipment input current up to and...
IEC 61000-3-3: Limits - Limitation of voltage changes, voltage fluctuations and flicker in public...
IEC 61000-3-11: Limits - Limitation of voltage changes, voltage fluctuations and flicker...
IEC 61000-3-12: Limits for harmonic currents produced by equipment connected to public...
IEC 61000-4-2: Electrostatic Discharge Immunity Test
IEC 61000-4-3: Radiated, radio-frequency, electromagnetic field immunity test
IEC 61000-4-4: Electrical Fast Transient (EFT) / EMC Burst Immunity Test Standard
IEC 61000-4-5: Testing and Measurement techniques - Surge Immunity Test
IEC 61000-4-6: Immunity to Conducted Disturbances, Induced by Radio Frequency Fields
IEC 61000-4-7: General Guide on Harmonics and Interharmonics Measurements and Instrumentation
IEC 61000-4-8 Electromagnetic Compatibility (EMC) - Part 4-8: Testing and Measurement Techniques...
IEC 61000-4-9 Electromagnetic Compatibility (EMC) - Part 4-9: Testing and Measurement Techniques...
IEC 61000-4-10: Testing and Measurement Techniques Damped Oscillatory Magnetic Field Immunity Test
IEC 61000-4-11: Testing and Measurement Techniques - Voltage Dips, Short Interruptions and...
IEC 61000-4-12: Testing and measurement techniques - Ring wave immunity test
IEC 61000-4-13: Testing and measurement techniques - Harmonics and interharmonics including mains...
IEC 61000-4-14: Testing and measurement techniques - Voltage fluctuation immunity test
IEC 61000-4-15: Testing and Measurement Techniques - Flickermeter. Functional and Design...
IEC 61000-4-16: Testing and Measurement Techniques – Test for Immunity to Conducted, Common Mode...
IEC 61000-4-17: Testing and measurement techniques - Ripple on d.c. input power port immunity test
IEC 61000-4-18: Testing and measurement techniques – Damped oscillatory wave immunity test
IEC 61000-4-19: Test for Immunity to Conducted, Differential Mode Disturbances and Signaling
IEC 61000-4-20 Electromagnetic compatibility (EMC) – Part 4-20: Testing and measurement techniques...
IEC 61000-4-21 Electromagnetic compatibility (EMC) Part 4-21: Testing and measurement techniques...
IEC 61000-4-27: Unbalance, immunity test
IEC 61000-4-28: Testing and measurement techniques - Variation of power frequency, immunity test
IEC 61000-4-29 Electromagnetic compatibility (EMC) - Part 4-29: Testing and measurement...
IEC 61000-4-30: Testing and Measurement Techniques - Power Quality Measurement Methods.
IEC 61000-4-31: Testing and measurement techniques - AC mains ports broadband conducted disturbance
IEC 61000-4-34: Testing and Measurement Techniques - Voltage Dips, Short Interruptions...
IEC 61000-4-39:2017: Electromagnetic Compatibility Immunity Requirements
IEC 61000-6-2: Immunity Testing of Industrial Equipment
IEC 61000-6-4: Emission standard for industrial environments
IEC 61000-6-5: Immunity for Power Station and Substation Environments
IEC 61010-1: Safety of Measuring, Control and Laboratory Equipment
IEC 61326: EMC Testing of Laboratory Equipment
IEC 61340-3-1: Methods for Replication of Electrostatic Effects - Human Body Model (HBM)...
IEC 61340-3-2: Methods for Replication of Electrostatic Effects – Machine Model (MM)...
IEC 61672-1: Electroacoustics – Sound level meters – Part 1: Specifications
IEC 61672-2: Electroacoustics – Sound level meters – Part 2: Pattern evaluation tests
IEC 61672-3: Electroacoustics – Sound level meters – Part 3: Periodic tests
IEC 61850: Communication Networks and Systems in Substations
IEC 62037: Passive RF and Microwave Devices, Intermodulation Level Measurement
IEC 62233: Electromagnetic Fields of Household Appliances and Similar Apparatus with Regard to Human
IEC 62619: Safety Requirements for Secondary Lithium Cells and Batteries, for Use in Industrial Applications
IEC 62764-1: Low-Frequency Magnetic Fields