Input Power |
90-264 VAC
47-63 Hz |
Source Configurations |
Voltage Source |
Power and Range |
3 X 150 VA 75, 150, 300V
6 X 75 VA 75, 150 V |
Each voltage source can be configured as a high power, low current range source to test high impedance ground/earth fault relays.
|
Power and Range |
3X150 VA 0.5, 1, 1.5 A
6X75 VA 0.5, 1 A
1X450 VA 1.5, 3, 6 A |
Accuracy |
< 0.02% typical |
Current Source |
Power and Range |
3 X 150 VA 7.5, 15, 30 A
6 X 75 VA 7.5, 15 A
1 X 450 VA 7.5, 15, 22.5, 30, 45, 90 A |
Accuracy |
< 0.02% Typical |
Each current source can be used in a transient mode which provides 50% more power at 2X current range
|
Phase Angle |
0 to + 359.9° (Lead)
0 to -359.9° (Lag) |
Accuracy |
< 0.1° typical |
Frequency |
Range |
DC to 3 kHz |
Accuracy |
0.5 PPM |
Number of Logic Inputs |
8 |
Number of Logic Outputs |
8 |
Operating |
Temperature |
0° to 50 °C / 32 ° 122°F |
Enclosure |
High impact, molded, flame retardant ABS - Meets National Safe Transit Association testing specification No. 1A for immunity to severe shock and vibration |
Dimensions |
15 X 9.5 X 18 inches |
Weight |
37.5 lb |