Input: |
120 V, 60 Hz, 15 A peak, 7.5 A average
(F) 230 V, 50/60 Hz, 8 A peak, 4 A average |
Output: |
0 – 62 kV AC peak, 0.1/0.05/0.02 Hz sinusoidal |
Duty: |
Continuous |
Load Rating: |
1.1 µF @ 0.1 Hz
2.2 µF @ 0.05 Hz
5.5 µF @ 0.02 Hz |
Voltmeter: |
0-65 kV AC peak |
Charging Current Meter: |
0 – 100 mA peak |
Load Capacitance Meter: |
0 – 6 µF |
Test Duration Timer: |
Programmable |
Output Termination: |
Shielded RG/8U output cable – 20 ft. (6 m)
Interconnect cable – 10 ft. (3 m) |
Size & Weight: (W x D x H) |
Controls:
26 x 13 x 16 in., 75 lb.
660 x 330 x 406 mm, 34 kg
HV Tank:
15 x 10.25 x 21.5 in., 120 lb.
381 x 260 x 546 mm, 45 kg |