Elgar 6006A 1000 VA 5000 Peak, AC Line Conditioner

Elgar 6006A 1000 VA 5000 Peak, AC Line Conditioner
Enlarge Image
Elgar Power Supplies 6006A
Request Quote Print Page

115V, 8.7A, 1kVA, AC Line Conditioner
 
Elgar Power Supplies 6006A Specs
  • Input Voltage Range: 94 - 138
  • Output:
    - Power (VA): Cont.: 1000; Peak: 5000
    - Voltage (VRMS): 115
    - Frequency (Hz): 57 - 63
  • Input/Output Isolation: 100 dB (60Hz)
  • Output Distortion: 0.2% max for up to 10% input harmonic distortion
  • Line Regulation: ± 0.025% for ± 10% input AC line variation
  • Load Regulation: ± 0.025% for no load/full load full current into unity to zero lagging or leading load
  • Reduces 500V 10µsec transients by 1000:1
  • Supplies peak currents 3.5 times RMS rating
  • Temperature coefficient: 0.005% per °C
  • Peak amplitude stability: ± 0.01% (cycle to cycle)
  • Amplitude drift: ± 0.05% 24 hrs constant line, load and temperature
  • Impulse settling time: less than 10µsec