Agilent N8900 Series Autoranging System DC Power Supplies

Rent Agilent N8900 Series Autoranging System DC Power Supplies
Enlarge Image
Request Quote Print Page
Datasheet
The Agilent N8900 Series Autoranging System DC Power Supplies provide 5, 10, and 15 kW single-output programmable DC power for ATE applications that require just the right amount of performance at just the right price. The N8900 Series power supplies’ autoranging output characteristic enables unprecedented flexibility by offering a wide range of voltage and current combinations at full power. Power supplies with “rectangular,” or traditional, output characteristics provide full power at only one voltage and current combination. Just one N8900 does the job of multiple power supplies. The N8900 Series provides stable output power, built-in voltage and current measurements, and autoranging output voltage and current from 80 to 1500 V and 10 to 510 A. These supplies offer many system-ready features like multiple standard I/O interfaces to simplify and accelerate test-system development and compact 3U design to save rack space. If more power is required, easily parallel multiple N8900 units to create “one” power supply with > 100 kW of total output power. The built-in master/slave control enables programming as if it’s just one big power supply; no need to program each supply individually.

*Please contact us with your specification requirements.

Specifications:


  N8920A / N8940A N8921A / N8941A N8923A / N8943A N8924A / N8944A N8925A / N8945A N8926A / N8946A N8928A / N8948A
DC Output Ratings:
Voltage 80 V 200 V 500 V 750 V 80 V 200 V 500 V
Current 170 A 70 A 30 A 20 A 340 A 140 A 60 A
Power 5 kW 5 kW 5 kW 5 kW 10 kW 10 kW 10 kW
Output Voltage Ripple and Noise:
CV p-p 100 mV 200 mV 250 mV TBD 150 mV 200 mV 300 mV
CV rms 14 mV 40 mV 70 mV TBD 10 mV 25 mV 70 mV
Load Effect: (change from 0% to 100% of full load)
Voltage 0.05% 40 mV 100 mV 250 mV 375 mV 40 mV 100 mV 250 mV
Current 0.15% 255 mA 105 mA 45 mA 30 mA 510 mA 210 mA 90 mA
Programming Accuracy:
Voltage 0.1% ≤ 80 mV ≤ 200 mV ≤ 500 mV ≤ 750 mV ≤ 80 mV ≤ 200 mV ≤ 500 mV
Current 0.2% ≤ 340 mA ≤ 140 mA ≤ 60 mA ≤ 40 mA ≤ 680 mA ≤ 280 mA ≤ 120 mA
Measurement Accuracy:
Voltage 0.1% ≤ 80 mV ≤ 200 mV ≤ 500 mV ≤ 750 mV ≤ 80 mV ≤ 200 mV ≤ 500 mV
Current 0.2% ≤ 340 mA ≤ 140 mA ≤ 60 mA ≤ 40 mA ≤ 680 mA ≤ 280 mA ≤ 120 mA
Load Transient Recovery Time:
Time ≤ 1.5 ms ≤ 1.5 ms ≤ 1.5 ms ≤ 1.5 ms ≤ 1.5 ms ≤ 1.5 ms ≤ 1.5 ms
  N8929A / N8949A N8930A / N8950A N8931A / N8951A N8932A / N8952A N8934A / N8954A N8935A / N8955A N8937A / N8957A
DC Output Ratings:
Voltage 750 V 1000 V 80 V 200 V 500 V 750 V 1500 V
Current: 40 A 30 A 510 A 210 A 90 A 60 A 30 A
Power 10 kW 10 kW 15 kW 15 kW 15 kW 15 kW 15 kW
Output Voltage Ripple and Noise:
CV p-p TBD 800 mV 150 mV 250 mV 300 mV TBD 1000 mV
CV rms TBD 350 mV 10 mV 25 mV 70 mV TBD 350 mV
Load Effect: (change from 0% to 100% of full load)
Voltage 0.05% 375 mV 500 mV 40 mV 100 mV 250 mV 375 mV 750 mV
Current 0.15% 60 mA 45 mA 765 mA 315 mA 135 mA 90 mA 45 mA
Programming Accuracy:
Voltage 0.1% ≤ 750 mV ≤ 1.0 V ≤ 80 mV ≤ 200 mV ≤ 500 mV ≤ 750 mV ≤ 1.5 V
Current 0.2% ≤ 80 mA ≤ 60 mA ≤ 1.1 A ≤ 420 mA ≤ 180 mA ≤ 120 mA ≤ 60 mA
Measurement Accuracy:
Voltage 0.1% ≤ 750 mV ≤ 1.0 V ≤ 80 mV ≤ 200 mV ≤ 500 mV ≤ 750 mV ≤ 1.5 V
Current 0.2% ≤ 80 mA ≤ 60 mA ≤ 1.1 A ≤ 420 mA ≤ 180 mA ≤ 120 mA ≤ 60 mA
Load Transient Recovery Time:
Time ≤ 1.5 ms ≤ 1.5 ms ≤ 1.5 ms ≤ 1.5 ms ≤ 1.5 ms ≤ 1.5 ms ≤ 1.5 ms