Megger TXL Extra Load Units for Torkel Test Systems

Rent Megger TXL Extra Load Units for Torkel Test Systems
Enlarge Image
Megger TXL
Request Quote Print Page
Datasheet Other1
These resistive extra loads do not perform any regulating functions. They are designed for use together with TORKEL battery load units. Their purpose is to provide higher load currents for use in constant current or constant power tests. Together, TORKEL and the TXL extra loads form a system that can discharge batteries with currents of up to several kA. TXL extra loads are connected directly to the battery, and TORKEL measures the total current using a clamp-on ammeter. TXL extra loads are shut down automatically when TORKEL is stopped.
 

Megger TXL Features:

 
  • ¬ĄProvide higher load currents for concurrent power tests
  • Discharging process controlled by a TORKEL unit
  • Connect directly to the battery under test
 
Models:
 
  TXL830 TXL850 TXL870
Max. voltage d.c. 28 V 56 V 140 V / 280 V
Max. current 300 A 300 A 112 A at 140 V
56 A at 280 V
Max. power 8.3 kW 16.4 kW 15.8 kW
Internal resistance, 3-position selector
Position 1 0.275 Ω 0.55 Ω 4.95 Ω
Current 100 A at 27.6 V (12 x 2.3 V) at 55.2 V (24 x 2.3 V) -
78.5 A at 21.6 V (12 x 1.8 V) at 43.2 V (24 x 1.8 V) -
50.1 A - - at 248.4 V (108 x 2.3 V)
39.2 A - - at 194.4 V (108 x 1.8 V)
Position 2 0.138 Ω 0.275 Ω 2.48 Ω
Current 200 A at 27.6 V at 55.2 V (24 x 2.3 V) -
156 A at 21.6 V 43.2 V (24 x 1.8 V) -
Position 3 0.092 Ω 0.184 Ω 1.24 Ω
Current 300 A at 27.6 V at 55.2 V (24 x 2.3 V) -
235 A at 21.6 V 43.2 V (24 x 1.8 V) -
100 A - - at 124.2 V (54 x 2.3 V)
78.4 A - - at 97.2 V (54 x 1.8 V)