Test Voltages |
500V, 1000V, 2500V, 5000V,
25-5000V in 25V steps |
Test Voltage Accuracy |
±5% on 10 MΩload & above
±25V for test voltages <500V
±12V for test voltages <125V |
Nominal Test Current Limit |
2mA or 5mA (Selectable)Charge |
Digital Measurement Resistance |
10kΩ - 500GΩ @500 V
10kΩ - 1TΩ @1000 V
10kΩt - 2, TΩ @2500 V
10kΩ - 5TΩ @5000 V |
Analogue Resistance Range |
0 kΩ - 1 TΩ |
Digital Voltage Range |
50-1000V a.c./d.c. (5000 V when testing) |
Digital Current Range |
0,01 nA to 999 μA |
Test Time |
15 seconds to 90 minutes |
Unit Dimensions |
12.8 x 12.4 x 7.7in. (327 x 316 x 196mm.) |
Unit Weight |
19.8 lbs. (9kg.) |