Sorensen SGA200/50E-0AAA 10KW DC Power Supply

Rent Sorensen SGA200/50E-0AAA 10KW DC Power Supply
Enlarge Image
Request Quote Print Page
Datasheet Other1

As part of the Sorensen SG Series, the SGA200/50E DC Power Supply, is available for customers requiring simple front panel analog controls or external control. With the same high performance power electronics as the SGI, the SGA provides essential features like 10- turn potentiometers for setting voltage and current, 3½ digit LED readout plus front panel over-voltage protection (OVP) preview/adjustment and reset.


Features:

  • High Power Density: Up to 15 kW in a 3U / 30 kW in a 6U chassis
  • Wide Voltage Range: 0-40V up to 0-600V, in increments of 5 kW from 5 to 30 kW 
  • Fast Load Transient Response: Protection from undesired voltage excursions 
  • Low RMS and P-P Noise: Suitable for the most sensitive applications 
  • Parallelable up to 150 kW: Expandable as your requirement grows 
  • Modular Design: Upgradeable for the ultimate in investment protection 
  • Sequencing: Program custom waveforms 
  • Easy-to-read Fluorescent Display: SGI supports English, French, German, Italian, Spanish, Chinese, Japanese, and Korean languages 
  • 16-bit Resolution: Optional IEEE-488.2 + RS-232C + Ethernet provides precise control 
  • Ethernet Control: LXI Class C compliant communication through integrated web server 
  • Direct Relay Control: Control output and sense isolation relays, along with polarity relays. (Ethernet Option Only) 
  • Hardware Trigger: Ethernet Option Only 
 

Specifications:

 
Common
Remote Sense Load-line loss compensation for models <= 100 V is 10% above full scale voltage total (5% per load-line), and models > 100 V is 4% above full scale voltage total (2% per load-line).
Parallel Operation Up to 5 units may be paralleled for additional current within the power supply single-unit specifications, with exception of the DC output current set accuracy. Additional paralleled SG units will add 0.3% inaccuracy per unit. To parallel more than 5 units, contact factory.
Series Operation Up to 2 units (see Output Float Voltage)
Input
Nominal Voltage
3 phase, 3 wire + ground
208/220 VAC (operating range 187 - 242 VAC)
380/400 VAC (operating range 342 - 440 VAC)
440/480 VAC (operating range 396 - 528 VAC)
Frequency 47 – 63Hz
Power Factor >0.9 typical at 208/220 VAC input
>0.78 typical at 380/400 VAC input
>0.69 typical at 440/480 VAC input
Protection ½ cycle ride-though on all three phases, 3 cycle ride through on single phase; missing phase shutdown
 
Applications:
 
  • Process Control
  • Product Development
  • Research
  • Automotive Component Test
  • Rackmount ATE Systems
  • Battery Charging