Short circuit / charge current |
3 mA @ 5 kV, 10 kV, and 15 k |
Digital |
10 kΩ to 30 TΩ |
Insulation test alarm |
100 kΩ to 10 GΩ |
Capacitor charge |
<7.5 s/μF at 3 mA to 15 kV |
Capacitor discharge |
<3500 ms/μF to discharge from 15 kV to 50 V |
Capacitance range |
10 nF to 50 μF |
Capacitance measurement accuracy |
±10% ±5 nF |
Current range |
0.01 nA to 6 mA |
Current accuracy |
±5% ±0.2 nA at all voltages (20°C) |
Interference |
6 mA from 2100 V to 15 kV |
Voltmeter range |
30 V to 660 V AC or DC, 45Hz – 65Hz |
Voltmeter accuracy |
±3%, ±3V |
Timer range |
Up to 99 minutes 59 seconds, 15 second minimum setting |
Test modes |
IR, IR(t), DAR, PI, SV, DD, and Ramp Test |
Operating temperature |
4°F to +122°F (-20°C to +50°C) |
Dimensions (L x W x H) |
360 x 305 x 194 mm (14.17 x 12 x 7.63 in) |