Dimensions
(W x H x L) |
21 in x 11 in x 30 in
53 cm x 28 cm x 76 cm |
Weight |
130 lb.
59 kg |
Voltage range |
100-240 Vrms, 50 or 60 Hz
1-phase or 3-phase Voltage is limited to 240 Vrms on some models |
Voltage configuration |
Single phase or 3-phase connection
Simultaneous voltage dropout testing
Voltage sag and swell testing
Phase selection front panel dial |
Event trigger input/output |
100 to 240 Vac (±10%)
50/60 Hz
4 Amps max |
Max instantaneous current recording |
±1000A instantaneous |
Resolution |
15 bits equivalent per individual sample on 1000V/1000A channels
12 bits per individual sample on other channels
16 bit equivalent for average and RMS measurements |
Accuracy |
Guaranteed accuracy ±1,0% FS on voltage and current
Typical accuracy ±0,25% FS (voltage and current)
±0,5% FS (power parameters)
±1,0% FS (harmonics)
±1° (between any voltage and current channel) |
Swell testing duration |
User-selected duration
From 1 cycle to 34 seconds in 1 cycle steps |
Sampling rate |
0.8 KHz-7.68 KHz |